Data cabling in a French tender specification (CCTP): six clauses to write

This article is written for projects run under French procurement practice, where each trade package (lot) is described in a technical specification called the CCTP. The data cabling package is known as the lot VDI (voice, data, video).

Network cabling accounts for a few per cent of the budget of a commercial building project and is often covered by a single line in the electrical package: “Category 6A cabling compliant with current standards”. The problems appear after move-in: links that underperform, outlets that cannot be found on the drawings, no test reports in the as-built file.

Cabling is kept for fifteen to twenty years. Redoing it in an occupied building costs far more than the original installation. Here is what should be written, whether the package is awarded to an electrician, to a specialist, or to an electrician working with a specialist.

1. Acceptance testing on 100% of links

Certification of every permanent link with a calibrated field certifier, to Class EA limits (ISO/IEC 11801, EN 50173), with results handed over in the instrument’s native format as well as in PDF. A continuity test does not prove that a link will carry 10 Gbit/s. Neither does sample testing (alien crosstalk aside): the defects are workmanship defects, link by link.

For fibre: insertion loss measurement and OTDR testing of every fibre.

2. A single system, from the panel to the outlet

Cable, connectors and panels from the same manufacturer and the same product range: this is what allows the class performance to be achieved over the whole link. Any product substitution during the works is subject to the written approval of the project’s lead consultant.

3. PoE and Wi-Fi planned at design stage

Wi-Fi access points, cameras, access control, displays: more and more equipment is powered over the network cable, up to 90 W at the switch port with IEEE 802.3bt (about 71 W at the device). The standard does not require Category 6A, but its copper cross-section and shielding limit heating, and it carries the multi-gigabit speeds of recent access points. Limit the size of cable bundles, which heat up, and allow two links per access point position, with ceiling outlets.

4. Properly sized technical rooms

The specification sets the usable dimensions, the dedicated power supply, the earthing of the rack, ventilation or air conditioning, and access control. The designer checks that the furthest outlet is no more than 90 m of cable away, along the real route; otherwise a second room is needed, and it is better to know that at sketch stage.

5. Coexistence with power cabling

Separate or partitioned routes, separation distances to EN 50174-2, equipotential bonding, bend radii, fill ratio of cable trays with spare capacity. None of this can be corrected once the ceilings are closed: plan a hold point before closure.

6. An as-built file the operator can use

As-built drawings with every outlet numbered, a schematic, a rack layout, a patching schedule, test reports for all links, datasheets of the installed products. Identical labelling at both ends, following a rule set in the specification.

Does it need a separate package?

Not necessarily. On a medium-sized project, a single power and data package simplifies coordination. What matters is that these requirements are written down, and that the company installing the data cabling, main contractor or subcontractor, is able to meet them. Ask to see the as-built file of a previous project.

Beyond a few hundred outlets, in occupied premises, or as soon as there is fibre between buildings, a separate data cabling package is justified.