You have set up sites before. The physics is the same in France; the way a project is organised, specified and handed over is not. These are the points that most often surprise IT and facilities managers working from abroad.
1. Your standard may say TIA; the local market says ISO
French specifications refer to ISO/IEC 11801 and EN 50173, and to EN 50174 for installation. Category 6A components give you a Class EA link: 10 Gbit/s over a 100 m channel (a 90 m permanent link plus patch cords), the same application as TIA Category 6A, with slightly tighter limits. Ask for certification against the limit your group actually uses, and say so in the order; a field certifier can test to either.
2. Expect shielded cable
Unshielded Cat 6A is common in North America. In France the default is shielded (F/FTP or similar), with shielded connectors and an earthed and bonded rack. It is not a problem, but mixing an unshielded group standard with locally sourced shielded products gives you a system that is neither one thing nor the other. Decide once, for the whole site.
3. Outlets and containment are local
Outlets are usually 45 × 45 mm modules clipped into trunking, floor boxes or desk power/data modules, not the faceplates your standard may show. Your part numbers may not exist here. A named European equivalent from the same manufacturer is usually the practical answer.
4. Cabling is often buried in the electrical package
On a French fit-out, the work is split into trade packages called lots. Data cabling is frequently part of the electrical package, described in a few lines, and priced by an electrician who may subcontract it. If you want it done to your standard, either require a separate data cabling package or have your requirements written into the specification (the CCTP): 100% link certification, one manufacturer end to end, labelling scheme, as-built documents.
5. Cable fire rating follows European rules
Permanently installed cable is classified under the EU Construction Products Regulation (Euroclass, from Aca to Fca, plus smoke, droplet and acidity criteria, for example Cca-s1,d1,a1). The class required depends on the building and its use. It is decided with the project’s fire safety consultant or inspection body (bureau de contrôle), not by the cabling contractor, and US plenum or riser ratings do not apply. Raise it early: it changes the part number and the price.
6. The landlord and the carrier work to their own timetables
In leased premises, core drilling, new riser routes or a rack in a shared technical room generally need the landlord’s written consent. The carrier’s fibre is ordered separately and its lead time runs to weeks, sometimes months. Neither is in the cabling contractor’s hands, and both are the usual reasons a site opens on 4G.
7. Site rules
A contractor working on your occupied site must go through a joint site inspection with you and, for longer or hazardous work, a written prevention plan (plan de prévention); on a construction site the equivalent is the contractor’s safety plan (PPSPS). Working at height or near live equipment requires specific training and employer-issued authorisations. For an industrial site, allow for a site safety induction for the installers. This is routine, but allow time for it in the schedule.
8. What handover should contain
The as-built file is called the DOE (dossier des ouvrages exécutés). Insist on: a test report for every link in the certifier’s native format, drawings with every outlet numbered, rack layouts, a patching schedule and the datasheets of the installed products. With native test files your network team can check the results without being on site.
A short checklist before you ask for quotations
- Floor plans with desks, meeting rooms and access point positions
- Your cabling standard, and the certification limit you expect
- Shielded or unshielded: decided
- Location of the comms room, and confirmation that the longest run is under 90 m
- Landlord consent and carrier order: who owns each
- Move-in date, and whether the premises will be occupied during the works